NEC Conductor Ampacity & Voltage Drop Sizer

Determine minimum copper or aluminum AWG size using NEC Table 310.16, NEC 110.14(C) terminal temperature limits, NEC 240.4(D) small-conductor rules, and NEC Chapter 9 Table 8 voltage drop.

Circuit Parameters

NEC Table 310.16 & Chapter 9 Table 8 Complete Reference (14 AWG – 4/0 AWG)

30°C Ambient / Not more than 3 current-carrying conductors
SizeArea (CM)Cu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C240.4(D) Cu Max
14 AWG4,11015 A20 A25 A— — — 15 A max
12 AWG6,53020 A25 A30 A15 A20 A25 A20 A max
10 AWG10,38030 A35 A40 A25 A30 A35 A30 A max
8 AWG16,51040 A50 A55 A30 A40 A45 AAmpacity-governed
6 AWG26,24055 A65 A75 A40 A50 A55 AAmpacity-governed
4 AWG41,74070 A85 A95 A55 A65 A75 AAmpacity-governed
3 AWG52,62085 A100 A115 A65 A75 A85 AAmpacity-governed
2 AWG66,36095 A115 A130 A75 A90 A100 AAmpacity-governed
1 AWG83,690110 A130 A145 A85 A100 A115 AAmpacity-governed
1/0 AWG105,600125 A150 A170 A100 A120 A135 AAmpacity-governed
2/0 AWG133,100145 A175 A195 A115 A135 A150 AAmpacity-governed
3/0 AWG167,800165 A200 A225 A130 A155 A175 AAmpacity-governed
4/0 AWG211,600195 A230 A260 A150 A180 A205 AAmpacity-governed

How PanelSpec Computes Wire Gauge & Voltage Drop

Conductor selection requires checking three sequential constraints rather than looking up one ampacity column in isolation:

  1. Governing Temperature Column (NEC 110.14(C)): Even when installing 90°C insulated wire such as THHN/THWN-2, circuit breaker lugs and residential panel terminals are normally rated at 75°C (or 60°C for Type NM-B cable per NEC 334.80). The calculator enforces the lower of the conductor insulation rating and equipment termination rating.
  2. Small-Conductor Overcurrent Limits (NEC 240.4(D)): Copper conductors rated 14 AWG, 12 AWG, and 10 AWG are capped at 15A, 20A, and 30A overcurrent devices respectively in general branch wiring, even though their 75°C/90°C ampacity values read higher.
  3. Circular-Mil Voltage Drop Check: Using NEC Chapter 9 Table 8 circular-mil areas and standard resistivity constants (K = 12.9 for copper, K = 21.2 for aluminum), PanelSpec automatically recommends stepping up one or more wire sizes when one-way distance drives voltage drop past your 3% branch or 5% feeder target.

Need deeper background on why 6 AWG Romex cannot supply a 60A EV charger circuit? Read our detailed guide on NEC Table 310.16 and the 75°C Terminal Trap.